Pump Tank Station | 1500 Gallon Capacity

Pump Tank Station | 1500 Gallon Capacity

TTK-1500
  • The Tough Tank® system is the revolutionary new design for pump tank systems, merging the non ferrous features of our patented polyethylene reservoir with the standard Advantage pumping system.
  • Tough Tank® is offered for Tower & Chilled Water systems. Tower systems are accommodated to 1000 tons and chilled water systems up to 600 tons.
  • All types of Industrial Applications can benefit from using the TTK Series pump tank station for plant wide water distribution. These include most Plastic molding processes, Diecasting, Dry Cleaning, Food Service and others.
  • Advantage offers Tough Tank® systems in capacities from 400 to 3000 gallon capacities.
Loading pricing...
Request A Price
1,475 GallonsReservoir Capacity
  • Specifications
  • Features
  • Options
  • Support Documents

Specifications

Reservoir Construction
Material: Polyethylene
Reservoir Capacity
To Overflow: 1475 Gallons
Operating (Tower): 750 Gallons
Operating (Chiller): 1125 Gallons
Maximum Recommended Flow
Total Flow: 1400 GPM
Connection Sizes
Water Make-Up: 1"
Drain: 1½"
Overflow: 6"
Dimensions
Height: 96"
Width: 72"
(tank) Depth: 74"
(2 pumps) Depth: 126"
(3 pumps) Depth: 133"
Weight
Tank Only (dry): 550 LBS
Tower (operating): 6,775 LBS
Chiller (operating): 9,888 LBS
To Overflow: 13,000 LBS
Specification Notes:
  1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
  2. Consult factory for assistance selecting pumps for your application.
  3. Dimensions are approximate and should be confirmed with the factory prior to construction planning.

Features

Reservoir

  • One piece, seamless, cylindrical shape
  • Rotational molded linear low density polyethylene that will not rust or corrode
  • Overflow port
  • Drain valve
  • Automatic water make up (float valve)
  • An internal baffle provides hot/cold water service (on 2 pump systems)
  • Hinged tank lid is included for easy access to the tank and to keep debris out
  • Sight tube provides level verification
  • 3/8″ dense foam insulation is applied to the outside of the reservoir on chilled water systems to prevent sweating and heat gain

Temperature Gauges

  • To process water temperature
  • From process water temperature (on 2 pump systems)

Warranty

  • 10 year tank failure warranty
  • 1 year on parts and labor on the pumping system

Pumps

  • Careful consideration to service, efficiency and motor protection are central to the design and selection of each pump
  • Nominal flow rates are 2.4 gallons per minute per ton for chilled water systems and 3 gallons per minute per ton for cooling tower systems
  • Process pumps are selected to provide 45-65 pounds per square inch of pressure
  • High efficiency centrifugal pumps are used for high flow to promote heat transfer
  • Full pump trim including suction & discharge valves are included and is constructed of Schedule 80 PVC or welded steel depending on pipe size and duty
  • Pumps providing higher flow rates and/or higher pressure are available
  • A pump discharge pressure gauge as well as starter and motor protection are included, assuring the pump tank station performs optimally and reliably

Options

Reservoir

  • Tank insulation (for tower water applications)

Variable Speed Drives

  • When used for pump control a pressure transducer senses process pressure and provides feedback to the drive to adjust the process flow rate to meet the current system needs
  • When used for cooling tower fan control a temperature transmitter senses the process water temperature and provides feedback to the drive to adjust the fan speed to meet the current cooling needs of the system
  • Based on settings, automatically uses the minimum energy necessary for the system saving energy, wear and money
  • A 20% motor speed reduction can save nearly 50% in pumping or fan energy

Temperature & Pressure Alarm

  • Pump pressure & fluid temperatures are constantly monitored
  • Out-of-spec activates audible and visual alarm

Space Saving System

  • Tough Tank reservoir is mounted on a frame above the pumping system to save valuable floor space
  • Many pump configurations are available that are designed to occupy the space below the tank

Standby Pump & Manifold

  • For process, tower or evaporator pumps
  • Standby pumps are pre-wired and manifolds are pre-plumbed
  • Provide uninterrupted operation when primary pump fails or requires maintenance

Central Control Console

  • In lieu of standard manual push button starters
  • Easier and less costly installation as well as operator convenience
  • All motor starters and controls are factory mounted in a NEMA 12 cabinet with branch circuit protection, control transformer and a single power connection
  • Power On light and off/on selector switches are mounted on cabinet door

Electric Water Level Control

  • Easier and less costly installation as well as operator convenience
  • The float switch is mounted outside of the reservoir in small enclosed tank positioned at proper operating water level
  • Being mounted outside of the main reservoir, the float switch tank is not affected by turbulence in the main reservoir making water level control more stable

Support Documents

Literature
Literature PDF for TTK-1500
Download
Updated on March 2019
Manual
Operating Manual for TTK-1500
Download
Updated on July 15, 2014