Pump Tank Station | 750 Gallon Capacity

Pump Tank Station | 750 Gallon Capacity

PTS-750-SS
  • These ready-to-run pump tanks are built from heavy-gauge steel and strengthened with perimeter reinforcement. Custom options are available to meet your specific application requirements.
  • Available for tower water systems (PTS) and chilled water systems (CPTS).
  • Advantage offers PTS/CPTS systems in capacities from 275 to 3000 gallons.
Loading pricing...
Request A Price
750 GallonsReservoir Capacity
  • Specifications
  • Features
  • Options
  • Support Documents

Specifications

Reservoir Construction
Material: Stainless Steel
Reservoir Capacity
To Overflow: 750 Gallons
Operating (Tower): 450 Gallons
Operating (Chiller): 565 Gallons
Maximum Recommended Flow
Total Flow: 675 GPM
Connection Sizes
Water Make-Up: 1"
Drain: 1½"
Overflow: 4"
Dimensions
Height: 79"
Width: 72"
(tank) Depth: 36"
(2 pumps) Depth: 80"
Weight
Tank Only (dry): 2,800 LBS
Tower (operating): 6,553 LBS
Chiller (operating): 7,512 LBS
To Overflow: 9,055 LBS
Specification Notes:
  1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
  2. Consult factory for assistance selecting pumps for your application.
  3. Dimensions are approximate and should be confirmed with the factory prior to construction planning.

Features

Pumps

  • Careful consideration to service, efficiency and motor protection are central to the design and selection of each pump
  • Nominal flow rates are 2.4 gallons per minute per ton for chilled water systems and 3 gallons per minute per ton for cooling tower systems
  • Process pumps are selected to provide 45-65 pounds per square inch of pressure
  • High efficiency centrifugal pumps are used for high flow to promote heat transfer
  • Full pump trim including suction & discharge valves are included and is constructed of Schedule 80 PVC or welded steel depending on pipe size and duty
  • Pumps providing higher flow rates and/or higher pressure are available
  • A pump discharge pressure gauge as well as starter and motor protection are included, assuring the pump tank station performs optimally and reliably

Options

Variable Speed Drives

  • When used for pump control a pressure transducer senses process pressure and provides feedback to the drive to adjust the process flow rate to meet the current system needs
  • When used for cooling tower fan control a temperature transmitter senses the process water temperature and provides feedback to the drive to adjust the fan speed to meet the current cooling needs of the system
  • Based on settings, automatically uses the minimum energy necessary for the system saving energy, wear and money
  • A 20% motor speed reduction can save nearly 50% in pumping or fan energy

Support Documents

Literature
Literature PDF for PTS-750-SS
Download
Updated on March 2019
Manual
Operating Manual for PTS-750-SS
Download
Updated on July 14, 2022