Air-Cooled | EDM Chiller | 2 Ton

Air-Cooled | EDM Chiller | 2 Ton

MG-2A-CH
  • Designed for indoor installation and provides between 20°F – 80°F fluid temperatures.
  • Includes an internal pumping system and reservoir.
  • Purpose built for the unique cooling needs of EDM machine applications.
  • Designed for indoor installation and air-cooled, using indoor ambient air to cool the process load. No plant or tower water is required.
  • Can be moved between applications and uses non ozone depleting refrigerant.
Loading pricing...
Immediate Pricing
2 TonsCooling Capacity
5Gallons/Minute (GPM)
  • Specifications
  • Features
  • Options
  • Control Instrument
  • Support Documents

Specifications

Unit Cooling Capacity
Tons: 2
kW: 7
Compressor
Horsepower: 2
Quantity: 1
Type: Scroll
Condenser
Type: Air-Cooled
Air Flow By: Fan
Fan Quantity: 1
CFM: 2000
Ambient: 95°F
Refrigerant
Type: R-454B
Classification: A2L (Lower Toxicity, Mildly Flammable)
Low Global Warming Potential (GWP)
Process Pump
Horsepower: ¾
GPM: 5
PSI: 30
Reservoir
Capacity: 7 Gallons
Process Connections
To Process: ¾"
From Process: ¾"
Full Load Amperage
230/3/60: 17
460/3/60: 8.5
Dimensions
Height: 30"
Width: 37"
Depth: 24"
Weight
Shipping: 400 LBS
Specification Notes:
  1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
  2. Cooling capacity: Rated tons at 12,000 BTU/hr/ton @ 50°F LWT Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.
  3. Ambient conditions: Loss of capacity and/or difficulty operating may occur at higher ambient temperatures. The minimum recommended ambient temperature is 60°F.

Features

Refrigerant Circuit

  • R-454B refrigerant
  • Scroll compressor
  • Microprocessor controlled 50% hot gas by-pass capacity control system
  • Air-Cooled condenser
  • Internal to Unit
  • Fan induced air flow
  • Brazed plate evaporator
  • Stainless steel plates
  • Copper brazing material
  • Refrigerant sight glass with moisture indicator
  • Filter-drier
  • Thermostatic expansion valve
  • Liquid line solenoid valve

Electrical

  • Nema 1 control cabinet
  • Compressor contactor
  • Process pump motor starter
  • Fused transformer
  • 10′ factory installed power cord with stain relief

Coolant Circuit

  • High flow centrifugal pump
  • Internal Reservoir
  • Insulated
  • Non-ferrous polyethylene construction
  • Reservoir lid is standard on this model
  • Standard NPT process fittings

System Limit Devices

  • High refrigerant pressure
  • Low refrigerant pressure
  • Process pump motor overload

Frame Construction

  • Compact physical size
  • Lift-off top cover panel
  • Stainless steel sheet metal
  • Castors – for portability
  • Designed for indoor installation

Pressure Gauges

  • Pressure is shown on the MG instrument display
  • Refrigerant head
  • Refrigerant low
  • Coolant

Warranty

  • 1 year covering parts and labor
  • Free preventative maintenance check in the 2nd year.
  • Warranty Document

Options

Electrical

  • Emergency Stop Button
  • UL508A Enclosed Electrical Panel
  • Power Disconnect (non fused)

Refrigerant Circuit

  • Condenser Screen

Control Instrument

  • Communications Upgrade : Modbus TCP

Coolant Circuit

  • Overhead Piping Kit
  • Process Line Shut Off Valves
  • Full Flow Bag Filter

Warranty

  • 4 year extended : 2 ton compressor (parts only)

Alarms

  • Beacon Alarm

Control Instrument

MG Series Control Instrument
  • Graphic LCD display with Intuitive Navigation
  • Digital refrigerant pressure display
  • Digital water pressure display
  • Plain language error message reporting
  • Controls hot gas bypass or digital scroll compressor for Capacity Control
  • Alarm output with audible signal
  • Industry 4.0 ready with Modbus RTU or SPI communication included, Modbus TCP communication optional
  • High water temperature shut down feature

Support Documents

Literature
Literature PDF for MG-2A-CH
Download
Updated on July 2023
Manual
Operating Manual for MG-2A-CH
Download