TYPICAL HANGER SPACING AND ROD DIAMETER FOR HORIZONTAL STEEL, PVC AND COPPER PIPING

  • Typical Hanger Types
  • Clevis Hanger
    Clevis Hange 1/2 to 30 in. pipe
  • Pipe Clamp
    Pipe Clamp 1/2 to 24 in. pipe
  • Double Bolt Pipe Clamp
    Double Bolt Pipe Clamp 3/4 to 36 in. pipe

Open or Close the descriptions below with the Open All Close All icons.

  • OpenCloseNominal Pipe Size : 3/8" - 1-1/4"
  • Rod Diameter : 3/8"
  • Steel : 7'
  • Schedule 40 : 4'
  • Schedule 80 : 4'
  • Copper : 5'
  • OpenCloseNominal Pipe Size : 1-1/2"
  • Rod Diameter : 3/8"
  • Steel : 9'
  • Schedule 40 : 5'
  • Schedule 80 : 5'
  • Copper : 8'
  • OpenCloseNominal Pipe Size : 2"
  • Rod Diameter : 3/8"
  • Steel : 7'
  • Schedule 40 : 4'
  • Schedule 80 : 4'
  • Copper : 5'
  • OpenCloseNominal Pipe Size : 2-1/2"
  • Rod Diameter : 1/2"
  • Steel : 11'
  • Schedule 40 : 6'
  • Schedule 80 : 6'
  • Copper : 9'
  • OpenCloseNominal Pipe Size : 3"
  • Rod Diameter : 1/2"
  • Steel : 12'
  • Schedule 40 : 6'
  • Schedule 80 : 7'
  • Copper : 10'
  • OpenCloseNominal Pipe Size : 3-1/2"
  • Rod Diameter : 1/2"
  • Steel : 13'
  • Schedule 40 : 6'
  • Schedule 80 : 7'
  • Copper : 11'
  • OpenCloseNominal Pipe Size : 4"
  • Rod Diameter : 5/8
  • Steel : 14'
  • Schedule 40 : 6'
  • Schedule 80 : 7'
  • Copper : 12'
  • OpenCloseNominal Pipe Size : 5"
  • Rod Diameter : 5/8"
  • Steel : 16'
  • Schedule 40 : 6'
  • Schedule 80 : 7'
  • Copper : 13'
  • OpenCloseNominal Pipe Size : 6"
  • Rod Diameter : 3/4"
  • Steel : 17'
  • Schedule 40 : 7'
  • Schedule 80 : 9'
  • Copper : 14'
  • OpenCloseNominal Pipe Size : 8"
  • Rod Diameter : 3/4"
  • Steel : 19'
  • Schedule 40 : 8'
  • Schedule 80 : 9'
  • Copper : 16'
  • OpenCloseNominal Pipe Size : 10"
  • Rod Diameter : 7/8"
  • Steel : 22'
  • Schedule 40 : 8'
  • Schedule 80 : 10'
  • Copper :
  • OpenCloseNominal Pipe Size : 12"
  • Rod Diameter : 7/8"
  • Steel : 23'
  • Schedule 40 : 9'
  • Schedule 80 : 11'
  • Copper :
  • OpenCloseNominal Pipe Size : 14"
  • Rod Diameter : 1"
  • Steel : 25'
  • Schedule 40 : 10'
  • Schedule 80 : 11'
  • Copper :
  • OpenCloseNominal Pipe Size : 16"
  • Rod Diameter : 1"
  • Steel : 27'
  • Schedule 40 : 10'
  • Schedule 80 : 11'
  • Copper :

The data provided should be used only as a reference and not as a quarentee of performance. Installation must conform with all local plumbing codes and regulations.

For more information about hanger spacing and rod diameters for steel, PVC and cooper piping call the Advantage Sales Department at 317-887-0729.

  • Download This Article
  • Download FYI 283
  • Download Now
  • 1 Page document
    in full color.
  • Acrobat PDF
    Size: 150 KB.

Need Application Assistance?

Our Experienced Team Can Save You Time & Money.

Tell Us About Your Project

Close