For plant wide distribution of chilled or tower water, Advantage recommends a system balance valve be installed between the “to process” and the “from process” lines.

The use of this valve prevents dead heading of the process pump in load or low flow situations.

Cash Acme K5 Valve
  • Advantage suggests the use of the CASH-ACME Type K-5 angle type back pressure valve.
  • The K-5 valve is a high capacity angle by-pass regulator or back pressure control valve.
  • System pressure to be regulated is connected to the bottom (inlet).
  • The system excess to be returned to the reservoir is connected to the side (outlet) as shown below.
  • K-5 installation diagram

Type K-5 is available in these sizes:

  • 1”
  • 1 1/4”
  • 1 1/2”
  • 2”

Features include:

  • Bronze body and trim
  • Screwed ends
  • Bottom and side female connections
  • Brass spring chamber
  • Stainless steel adjustment spring
  • Asbestos gaskets.
  • Type K-5C has a silicone rubber seat disc to provide for tight shut-off.

This valve or an equivalent can be obtained at a local plumbing supply house.

The K-5 can also be used to maintain a certain pressure difference across the process. The adjustable spring provides for various pressure settings within its range. See capacity information below. Maximum temperature is 400°F.

K5 valve dimensions

For more information on K-5 Valves for Process Cooling Systems call the Advantage Sales Department at 317-887-0729