The Tough Tank® system is the revolutionary new design for pump tank systems, merging the non ferrous features of our patented polyethylene reservoir with the standard Advantage pumping system.
Tough Tank® is offered for Tower & Chilled Water systems. Tower systems are accommodated to 1000 tons and chilled water systems up to 600 tons.
All types of Industrial Applications can benefit from using the TTK Series pump tank station for plant wide water distribution. These include most Plastic molding processes, Diecasting, Dry Cleaning, Food Service and others.
Advantage offers TOUGH TANK® systems in capacities from 400 to 3000 gallon capacities.
SPECIFICATIONS
TTK-1500
Water Capacity
To Overflow : 1,475 gal
Operating (Tower) : 750 gal
Operating (Chiller) : 1,125 gal
Maximum Recommended Flow
Total Flow : 1400 GPM
Connection Sizes
Water Make-Up : 1"
Drain : 1.5"
Overflow : 6"
Dimensions
Height : 96"
Width : 72"
(tank) Depth : 74"
(2 pumps) Depth : 126"
(3 pumps) Depth : 133"
Weight (3)
Tank Only Dry : 550 lbs
Tower Operating : 6,775 lbs
Chiller Operating : 9,888 lbs
To Overflow : 13,000 lbs
Specification Notes:
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
3. Typical process pumps are shown. Several HP ranges can be used on this unit. However, the most typical are displayed here for reference. Consult the factory for specific HP and GPM requirements.
3. Displayed weight data does not include the weight of pumps or controls.
Pump Specifications shown here are provided for representation of capacity. Consult with Advantage for specific pumps to use with your process. Evaporator Pumps are provided for Chilled water systems. Tower pumps are provided for Tower water systems.
Process Pump (Pumps listed are suitable for use with this reservoir)Close
PP-2
PP-3
PP-5
PP-7.5
PP-10
PP-15
PP-20
PP-25
PP-30
PP-40
PP-2
Capacity
HP : 2
GPM : 40
PSI : 40
Full Load Amperage (1)
230/3/60 : 6.8
460/3/60 : 3.4
575/3/60 : 2.7
PP-3
Capacity
HP : 3
GPM : 60
PSI : 48
Full Load Amperage (1)
230/3/60 : 9.6
460/3/60 : 4.8
575/3/60 : 3.9
PP-5
Capacity
HP : 5
GPM : 90
PSI : 48
Full Load Amperage (1)
230/3/60 : 15.2
460/3/60 : 7.6
575/3/60 : 6.1
PP-7.5
Capacity
HP : 7.5
GPM : 150
PSI : 58
Full Load Amperage (1)
230/3/60 : 22.0
460/3/60 : 11.0
575/3/60 : 9.0
PP-10
Capacity
HP : 10
GPM : 210
PSI : 60
Full Load Amperage (1)
230/3/60 : 28.0
460/3/60 : 14.0
575/3/60 : 11.0
PP-15
Capacity
HP : 15
GPM : 300
PSI : 60
Full Load Amperage (1)
230/3/60 : 42.0
460/3/60 : 21.0
575/3/60 : 17.0
PP-20
Capacity
HP : 20
GPM : 405
PSI : 60
Full Load Amperage (1)
230/3/60 : 54.0
460/3/60 : 27.0
575/3/60 : 22.0
PP-25
Capacity
HP : 25
GPM : 525
PSI : 55
Full Load Amperage (1)
230/3/60 : 68.0
460/3/60 : 34.0
575/3/60 : 27.0
PP-30
Capacity
HP : 30
GPM : 600
PSI : 53
Full Load Amperage (1)
230/3/60 : 84.0
460/3/60 : 42.0
575/3/60 : 32.0
PP-40
Capacity
HP : 40
GPM : 810
PSI : 63
Full Load Amperage (1)
230/3/60 : 104.0
460/3/60 : 52.0
575/3/60 : 41.0
Evaporator Pump (Pumps listed are suitable for use with this reservoir)Close
EP-2
EP-3
EP-5
EP-7.5
EP-10
EP-15
EP-20
EP-2
Capacity
HP : 2
GPM : 60
PSI : 25
Full Load Amperage (1)
230/3/60 : 6.8
460/3/60 : 3.4
575/3/60 : 2.7
EP-3
Capacity
HP : 3
GPM : 90
PSI : 25
Full Load Amperage (1)
230/3/60 : 9.6
460/3/60 : 4.8
575/3/60 : 3.9
EP-5
Capacity
HP : 5
GPM : 210
PSI : 25
Full Load Amperage (1)
230/3/60 : 15.2
460/3/60 : 7.6
575/3/60 : 6.1
EP-7.5
Capacity
HP : 7.5
GPM : 255
PSI : 25
Full Load Amperage (1)
230/3/60 : 22.0
460/3/60 : 11.0
575/3/60 : 9.0
EP-10
Capacity
HP : 10
GPM : 405
PSI : 25
Full Load Amperage (1)
230/3/60 : 28.0
460/3/60 : 14.0
575/3/60 : 11.0
EP-15
Capacity
HP : 15
GPM : 525
PSI : 24
Full Load Amperage (1)
230/3/60 : 42.0
460/3/60 : 21.0
575/3/60 : 17.0
EP-20
Capacity
HP : 20
GPM : 810
PSI : 25
Full Load Amperage (1)
230/3/60 : 54.0
460/3/60 : 27.0
575/3/60 : 22.0
Tower Pump (Pumps listed are suitable for use with this reservoir)Close
TP-2
TP-3
TP-5
TP-7.5
TP-10
TP-15
TP-20
TP-2
Capacity
HP : 2
GPM : 60
PSI : 25
Full Load Amperage (1)
230/3/60 : 6.8
460/3/60 : 3.4
575/3/60 : 2.7
TP-3
Capacity
HP : 3
GPM : 90
PSI : 25
Full Load Amperage (1)
230/3/60 : 9.6
460/3/60 : 4.8
575/3/60 : 3.9
TP-5
Capacity
HP : 5
GPM : 210
PSI : 25
Full Load Amperage (1)
230/3/60 : 15.2
460/3/60 : 7.6
575/3/60 : 6.1
TP-7.5
Capacity
HP : 7.5
GPM : 255
PSI : 25
Full Load Amperage (1)
230/3/60 : 22.0
460/3/60 : 11.0
575/3/60 : 9.0
TP-10
Capacity
HP : 10
GPM : 405
PSI : 25
Full Load Amperage (1)
230/3/60 : 28.0
460/3/60 : 14.0
575/3/60 : 11.0
TP-15
Capacity
HP : 15
GPM : 525
PSI : 25
Full Load Amperage (1)
230/3/60 : 42.0
460/3/60 : 21.0
575/3/60 : 17.0
TP-20
Capacity
HP : 20
GPM : 810
PSI : 25
Full Load Amperage (1)
230/3/60 : 54.0
460/3/60 : 27.0
575/3/60 : 22.0
FEATURES
Reservoir:
One piece, seamless, cylindrical shape
Rotational molded linear low density polyethylene
Overflow port
Drain valve
Automatic water make up (float valve)
Hot / cold section partition (on 2 pump systems)
Tank Lid
Temperature Gauges:
To process water temperature
From process water temperature (on 2 pump systems)
Warranty:
1 year on parts and labor on the pumping system
10 year tank failure
OPTIONS
Reservoir
Tank insulation (for chilled water applications)
Central Control Console
Mandatory purchase for Alarm, Water Make-Up and Digital Temperature display options
Image is typical. Actual unit appearance will vary according to specifications and options.
-
Need Application Assistance?
Our Experienced Team Can Save You Time & Money.
Tell Us About Your Project
Close
This site uses cookies to offer you a better browsing experience. Learn more about how Advantage Engineering, Inc. uses cookies by contacting the site
administrator at admin@advantageengineering.com By closing this banner, scrolling this page, clicking a link or continuing to browse otherwise, you agree to the use of cookies.
Please refer to the Advantage Engineering Privacy Policy.