Specifications
Model: MG-25ARC (1)
Unit Cooling Capacity
(2)Tons : 23.1
kW : 81
Compressor
HP : 25
Quantity : 1
Type : Scroll
Refrigerant
Type : R-410A
Process Pump
HP : 5
GPM : 60
PSI : 59
Type : Centrifugal
Construction :
Reservoir
Capacity : 65 gallons
Construction : Standard
Process Connections
To Process : 2"
From Process : 2"
Water Make Up : 1/2"
Full Load Amperage(3)
230/3/60 : 106
460/3/60 : 53
575/3/60 : 43
Dimensions
Height : 57"
Width : 34"
Depth : 80"
Weight(4)
Shipping : 2,100 lbs
Specification Notes:
Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/- 5% as reserved by the compressor manufacturer. Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.
Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.
Unit weight crated for shipping.
Remote Condenser (1)
Capacity(2)
R410A @ 1° TD : 20.03 MBTU/hr
R410A @ 20° TD : 26.71 tons
Circuits Served
Maximum : 1
Fans
Quantity : 3
RPM : 1,140
Connections(3)
Gas : 2-5/8"
Liquid : 2-1/8"
Full Load Amperage(4)
460/1/60 : 8.5
Construction
Tube Material : Copper
Fin Material : Aluminum
Coating : None
Fins Per Inch : 8
Dimensions
Height : 54"
Width : 44-5/8"
Depth : 167-1/2"
Weight(5)
Shipping : 1,050 lbs
Reference : KCL-41-KR
Remote Condenser Specification Notes:
Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ " 115°F condensing temperature. Capacities may be +/- 5% as reserved by the compressor manufacturer. Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.
Field charging by user required.
Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.