Product Overview
Air-cooled central chillers use mechanical refrigeration to cool recirculated fluid that support industrial process cooling applications.
20°F to 70°F process fluid temperature range.
Titan systems combine one or more refrigeration circuits with a large capacity reservoir and pumping system assembled on a single skid for low ease of installation.
Air-cooled chillers use ambient air to dissipate the heat from the refrigeration system.
The refrigeration system, controls, reservoir and pumping system remain inside while the remote air-cooled condenser is located outside.
Assembled from known reliable and long service life components, this water chiller will operate efficiently for many years in many types of industrial environments.
Price is Loading
Specifications
Model: TI-40A (1)
Refrigerant Zones
Quantity : 2
Compressor
Quantity : 2
Horsepower : 20
Type : Scroll
(2)Total Capacity : 40 tons
Refrigerant
Type : R-410A
Process Pump(3)(4)
Horsepower : 7.5
GPM : 98
PSI : 60
Evaporator Pump(3)(4)
Horsepower : 3
GPM : 96
Full Load Amperage(5)(6)
230/3/60 : 190
460/3/60 : 95
575/3/60 : 76
Reservoir Capacity
Operating : 340 gallons
Holding : 400 gallons
Connection Sizes
To Process : 3"
From Process : 3"
Water Make-Up : 1"
Overflow : 4"
Condesner : "
Dimension
Height : 82"
Width : 92"
Depth : 96"
Weights
(7)Shipping : 4,350 lbs
Operating : 8,710 lbs
Specification Notes:
Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40.
Consult pump curve for exact pump performance.
Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ " 115°F condensing temperature. Capacities may be +/- 5% as reserved by the compressor manufacturer. Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.
Field charging by user required.
Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.