Advantage OACS air-cooled central chillers use mechanical refrigeration to cool recirculated fluid that support industrial process cooling applications.
20°F to 70°F fluid temperature range.
OACS air-cooled water chillers use ambient air to dissipate process heat and efficiently runs in air temperature between -20°F to 95°F.
OACS systems are designed for outdoor installation in most types of climates. The air-cooled condenser, chiller zones, reservoir and pumping system are delivered as a complete package.
PRICING
SPECIFICATIONS
OACS-20S-MG-1P
Refrigerant Zones
Quantity : 1
Capacity
(2) Tons : 18.7
kW : 65.7
Compressor
Type : Scroll
Refrigerant
Type : R-410A
Air-Cooled Condenser
# of Fans : 2
Evaporator
Type : Brazed Plate
Process Pump
(3) HP : 3
(4) GPM : 48
PSI : 48
Standby Pump
Offered : Available
Reservoir Capacity
Capacity : 68 gal
(5) Construction : PE
Connection Sizes
Type : 2"
Size : NPT"
Dimensions (6)
Height : 87"
Width : 54"
Depth : 127"
Controller
Instrument Type : MG
System Amperage (7)
460/3/60 : 52.0
Specification Notes:
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40.
The minimum recommended operating temperature when no glycol is used is 48°F.
3. Consult pump curve for exact pump performance.
4. Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
5. PE = polyethylene; SS = stainless steel; MS = epoxy coated mild steel.
6. Approximate dimensions. Not for construction purposes.
7. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
FEATURES
Refrigerant Circuit:
Non-Ozone depleting refrigerant
Single scroll compressor
Compressor suction service valve
Compressor discharge service valve
Brazed Plate evaporator
Integral air-cooled condenser - with variable speed fans - with pressure staging
Liquid receiver
Liquid line solenoid valve
Refrigerant sight glass with moisture indicator
Thermostatic expansion valve
Capacity control
Electrical:
Outdoor rated electrical cabinet
Fused transformer
Fused pump motor starters
Power entry terminal block
Fused compressor motor starters
Pressure Gauges:
Refrigerant high pressure
Refrigerant Low Pressure
Coolant pressure
Coolant Circuit:
Large capacity process pump - suction service valve - discharge service valves
Image is typical. Actual unit appearance will vary according to specifications and options.
-
Need Application Assistance?
Our Experienced Team Can Save You Time & Money.
Tell Us About Your Project
Close
This site uses cookies to offer you a better browsing experience. Learn more about how Advantage Engineering, Inc. uses cookies by contacting the site
administrator at admin@advantageengineering.com By closing this banner, scrolling this page, clicking a link or continuing to browse otherwise, you agree to the use of cookies.
Please refer to the Advantage Engineering Privacy Policy.