Cooling Tower
Model: TC-540F
Specifications
Have A Question?
Call 317-887-0729
for your answer.
--
PRODUCT SPECIFICATIONS
Model: TC-540F (1)
(2) Capacity
Capacity;
540 tons
Flow Rate:
1,620 GPM
Direct Drive Fan
Quantity:
4
RPM:
870
CFM:
122,000
Motor
Quantity:
4
HP:
30
(3)(4) Full Load Amperage
230/3/60:
112.0
460/3/60:
56.0
575/3/60:
48.0
(5) Connection Sizes
To Tower:
2 @ 6"
From Tower:
2 @ 10"
Dimensions
Height:
140"
Width:
338"
Depth:
96"
Weight
Dry:
5,800 lbs
Operation:
15,000 lbs
Shipping:
6,800 lbs
Specification Notes::
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change with notice or liability. Selection of certain optional features may change listed specifications.
2. Cooling water from 95°F to 85°F at 3 gpm per ton and 78°F web bulb temperature.
3. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
4. Consult factory for 50HZ operation.
5. When used with remote sump consult factory for connection size when the base of the tower will be used as the reservoir.
6. See
Product Warranty Statement W-700 for details on warranty.

TC-540F (typical)
Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142 Phone: 317-887-0729 Fax: 317-881-1277
Privacy Statement: we will not sell, rent or release any personal information you share with us to third party vendors.
Sitemap Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability.
Products are assembled in the United States of America.
© 2013 ADVANTAGE ENGINEERING, INC
Advantage Engineering Provides Industry Process Cooling Equipment For Optimizing Your Process