FRAME CONSTRUCTION:
• Powder coated steel upright frame
• Galvanized steel cross frame
• Powder coated steel lift-off cabinetry
• Lift-off top panel
• Thermoformed ABS front fascia
• Compact physical size
• Castors - for portability

REFRIGERANT CIRCUITS:
• Scroll compressor
• Full component insulation
• Air-cooled condenser with finned tubes
• Centrifugal Blower
• Refrigerant sight glass with moisture
  indicator
• Filter-drier
• Liquid line solenoid valve
• Refrigerant sight glass with
  moisture indicator
• Thermostatic expansion valve
• Brazed plate evaporator
• Capacity control (via hot gas
  bypass)

COOLANT CIRCUIT:
• High flow centrifugal pump
• Large capacity insulated non-ferrous
  reservoir
• Reservoir level sight glass
• Automatic water make-up system
• Standard NPT process fittings

PRESSURE GAUGES:
• Refrigerant high pressure
• Refrigerant low pressure
• Coolant pressure

ELECTRICAL:
• Process pump motor starter
• Compressor motor starter
• Fused transformer
• NEMA rated electrical cabinet
• Power entry terminal block

SYSTEM LIMIT DEVICES:
• High pressure limit
• Low pressure limit
• Coolant freezestat
• Process pump motor overload
• Internal compressor overload
• Control circuit fuse

WARRANTIES:
• 1 year on parts and labor

CHILLER CONTROL INSTRUMENT
Portable Chiller M1 Instrument
M1 Series (standard instrument)
• Continuous To Process temperature
  display
• Selectable Setpoint temperature
  display
• Illuminate ON/OFF power switch
• Soft touch Setpoint selection keys
• Bright and easy-to-read LCD
  Temperature display window
• Machine Status with Compressor
  and Capacity Control indicating
  lights
• Basic Machine Diagnostics with
  Refrigeration Fault indicating
  light

OPTIONS

LE Instrument for Maximum Portable Process Liquid Chillers
CHILLER CONTROL INSTRUMENT
LE Series

• Continuous To Process and
  Setpoint temperature display
• Selectable From Process
  temperature display
• Temperature display in Fahrenheit
  or Celsius
• Status indicators for Power On,
  Compressor, Bypass/Unload,
  Alarm, Reservoir Level, Freezestat,
  Refrigerant circuit, and Low Flow
• Soft key operators
• RS-485 SPI communications port
  with display indication

REFRIGERANT CIRCUIT:
• Compressor CPR valve
  (for setpoints above 65°F)

COOLANT CIRCUIT:
• Overhead piping kit : factory or
  field installed
• No reservoir tank for gravity
  return applications
• Low flow bypass valve : manual
  or automatic
• Process line shut-off valves
• Larger process pumps

SYSTEM SAFETY DEVICES:
• Audible alarm
• Visual / audible alarm beacon

WARRANTIES:
• Extended compressor warranty

ELECTRICAL:
• Branch circuit fusing

Click For Maximum Liquid Chiller Pricing
Immediate Online Pricing
for the M1-30A

SPECIFICATIONS

Model: M1-30ASL

 
(2) CAPACITY
TONS:
KW: SL
COMPRESSOR
HP:
TYPE:SL
PROCESS PUMP
HP:
GPM:
PSI:
TYPE:
CONSTRUCTION: SL
CONNECTION SIZES
TO:
FROM:
WATER MAKE-UP: SL
AIR-COOLED CONDENSER
TYPE:
CFM:
(3) AMBIENT:
(6) SP:
SL
(4) FULL LOAD
AMPERAGE

230/3/60:
460/3/60:
575/3/60SL
TANK CAPACITY
HOLDING:
LID:
AUTO MAKE-UP:
SL
DIMENSIONS
Height:
Width:
Depth: SL
(5) WEIGHT
Shipping:

   
30
105.5
SL
 
15 x 2
Scroll SL
 
5
72
57
Centrifugal
Stainless Steel SL
 
2"
2"
1/2" SL
 

Blower
30,000
95 °F
1.35 SL
 
 

178
89
72
SL
 
65"
Standard"
Standard" SL
 
96"
58"
70" SL
 
2,900 lbs

Specification Notes:
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liabililty. Selection of certain optional features may change listed specifications.
2. Tons capacity at 12,000 BTU/ton @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40. The minimum recommended operating temperature when no glycol is used is 48°F.
3. Design ambient conditions. Loss of capacity and/or difficulty operating will occur at higher ambients.
4. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.
5. Unit weight crated for shipment.
6. Static pressure in inches of water.

Look at Specifications for all Air-Cooled Models

Advantage Products

LITERATURE

Maximum Portable Chiller Literature : PDF File to Download
All Models
PDFPDF Document
Color, 6 Pages
File Size: 180 KB

SERVICE MANUAL
Registration required
to download.

Maximum Portable Chiller Literature : PDF File to Download
5 - 40 Ton Units
PDFPDF Document
M1 Chiller Control
Color, 70 pages
File Size: 613 KB


Knowledge Base
PDF HTMLPDF & HTML
Documents covering the selection, service & operation of portable liquid chillers.