RERFIGERANT LINE PIPE SIZING FOR REMOTE CONDENSER

Use these charts to select the proper piping size for refrigerant lines to remote air-cooled condenser. Click on the charts below to open a larger view with instructions.

Please Note : these charts are for R-22 refrigerant only.

Liquid Line
image
Open This Chart

Hot Gas Line
chart
Open This Chart

LIQUID LINES (Chart A)

Please Note : this chart is for R-22 refrigerant only.

Step 1. Assume an equivalent feet of pipe. Usually estimate the run and multiply by 1.5 to account for elbows, ect.

Step 2. Using estimated equivalent feet from Step 1, enter chart A and pick line size required. Pick the closest next larger size when your point falls between two line sizes.

Step 3. Using the line size selected above, calculate actual equivalent feet using table 1.

Step 4. Compare actual equivalent feet with estimated equivalent feet. If actual is less than or equal to estimated, your selection is good. If actual is more than estimated, enter chart A to be sure it is still a good selection. Reselect if necessary.

image

Close Window

For more information about liquid chiller refrigerant line sizing for remote air-cooled condensers call the Advantage Sales Department at 317-887-0729.

Serving Plastics and Industrial Markets since 1977
American Flag
Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142   Phone: 317-887-0729   Fax: 317-881-1277
Privacy Statement: we will not sell, rent or release any personal information you share with us to third party vendors.   Sitemap   
Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability.
Products are assembled in the United States of America.
©2014 ADVANTAGE ENGINEERING, INC
Advantage Engineering Provides Industry Process Cooling Equipment For Optimizing Your Process