WPT Series process water chilling modules provide chilled fluids between
20°F and 70°F (-7°C - 26°C) for cooling
industrial process applications between 5 and 180 tons. WPT Series models are built onto an open frame for easy access to all serviceable parts.

STANDARD FEATURES
REFRIGERANT CIRCUIT (per zone):
• Scroll compressor
• Compressor suction service valve
• Compressor discharge service valve
• Shell and tube evaporator
• Water-cooled condenser with
removable heads for service
• Condenser regulator valve
• Liquid line solenoid valve
• Refrigerant sight glass with
moisture indicator
• Thermostatic expansion valve
• Cylinder Unloading
• Non-Ozone depleting refrigerant
LIMIT DEVICES (per zone):
• Refrigerant high pressure
• Refrigerant low pressure
• Evaporator flow
• Instrument circuit fuse
PRESSURE GAUGES (per zone):
• Refrigerant high Pressure
• Refrigerant low Pressure
• Coolant pressure
WARRANTY (US & Canada)
• 1 year parts and labor
ELECTRICAL
• Fused transformer
• Nema rated electrical cabinet
• Power entry terminal block
• Fused compressor motor starter on
dual and triple zone units
OPTIONS
REFRIGERANT CIRCUIT
• Compressor CCPR valve for fluid
temperatures above 65°F
• Compressor hour meter
CHILLER CONTROL INSTRUMENT
• Remote display kit
• PLC with touch screen display
WARRANTIES
• Extended compressor warranty
ELECTRICAL
• UL listed electrical panel
• Disconnect
SPECIFICATIONS
Model: C-60WPT (1) ![]()
Specification Notes:
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liabililty.
Selection of certain optional features may change listed specifications.
2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 105°F condensing temperature. Capacities may be +/5% as reserved by
the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40.
The minimum recommended operating temperature when no glycol is used is 48°F.
3. Flow rate (GPM) is based on 60°F city water source with a clean condenser.
4. Flow rate (GPM) is based on 85°F tower water source with a clean condenser.
5. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
6. Consult factory for 50HZ operation.
7. Unit weight crated for shipment.
8. See Warranty Statement #W-700 for details.
STANDARD INSTRUMENT CONTROLLER

• Microprocessor based controller
• Continuous To Process temperature display
• Continuous Setpoint temperature display
• Large temperature display windows
• °F or °C temperature display
• Selectable from process temperature display
• Machine indicators for Power On, Compressor, Bypass,
Alarm, Freezestat, Refrigerant Circuit,
and Low Flow
• Soft Key Operators
• SPI communications
• Audible and visual alarm