CENTRAL CHILLER


60 Tons : Titan Series : Specifications, Features & Options

Get an Immediate Online Price Quote for this Sentra Series temperature temperature control unit now

Titan Series multi zone water-cooed process liquid chillers provide chilled fluilds between
20°F and 70°F.20-70 ton central liquid chiller Titan Series
Click to view larger image.
Titan 20-70 Tons Titan 20-70 Tons Titan

STANDARD FEATURES

RESERVOIR:
• Seemless rotationally molded polyethylene
• Insulation
• Drain valve
• Overflow port
• Hot / cold section baffle
• Structural base
• Pump decking
• Automatic water level control
• Spare pump ports
• Hinged tank cover

REFRIGERANT CIRCUIT:
• Scroll compressor
• Compressor suction service valve
• Compressor discharge service valve
• Brazed plate evaporator
• Water-cooled condenser
    - with regulator valve
    - with manifold with isolation valves
    - with removable heads
• Liquid line solenoid valve
• Refrigerant sight glass with
  moisture indicator
• Thermostatic expansion valve
• Capacity control via hot gas bypass
• Non-Ozone depleting refrigerant

COOLANT CIRCUIT
• Large capacity process pump
     - Suction service valve
     - Discharge service valve
• Evaporator pump
     - Suction service valve
     - Discharge service valve

LIMIT DEVICES (per zone)
• Refrigerant high pressure
• Refrigerant low pressure
• Evaporator flow
• Instrument circuit fuse

PRESSURE GAUGES (per zone)
• Refrigerant high Pressure
• Refrigerant low Pressure
•Coolant pressure

WARRANTY (US & Canada)
• 1 year parts and labor
• 2nd year complementary
  preventative maintenance visit

CONTROL INSTRUMENT Multizone liquid chiller control instrument
Learn More about this instrument.

• Microprocessor based multizone controller
• Intelligent zone boards
• Compressors are staged individually
• Continuous To Process temperaturedisplay
• Continuous Setpoint temperaturedisplay
• Selectable from processtemperature display
• Large temperature display windows
• °F or °C temperature display
• Refrigerant circuit indicators for Probe, Low Flow, High Pressure, Low Pressure, Compressor,Freezestat, Capacity Control
• Water circuit indicators for Temperature Deviations, Low Pressure, Tank Level, Probe, Phase
• Selectable lead - lag mode
• Soft Key Operators
• SPI communications
• Audible and visual alarm

OPTIONS

FRAME
• Special Paint
• Stainless Steel Reservoir
• Epoxy coated mild steel reservoir

REFRIGERANT CIRCUIT
• Compressor CCPR valve
• Compressor hour meter

COOLANT CIRCUIT
• Larger process pumps
• Standby pump and manifold

CHILLER CONTROL INSTRUMENT
• Remote display kit
• PLC with touch screen display

WARRANTIES
• Extended compressor warranty

ELECTRICAL
• UL listed electrical panel
• Disconnect

SPECIFICATIONS

Model: TI-60WSM

 
REFRIGERANT ZONES
Quantity: SO
COMPRESSOR
Quantity:
HP:
Type:
(1) Total Capacity: SO
(2) (3) PROCESS PUMP
HP:
GPM:
PSI: SO
EVAPORATOR PUMP
HP:
GPM: SO
CONNECTION SIZES
To Process:
From Process:
Make-Up:
Overflow:
Condenser: SO
WATER-COOLED
CONDENSER

(4) From City:
(5) From Tower: SO
(6) (7) FULL LOAD
AMPERAGE

230/3/60:
460/3/60:
575/3/60: SO
REFRIGERANT
Type HFC: SO
RESERVOIR CAPACITY
Operating:
Holding: SO
DIMENSIONS
Height:
Width:
Depth: SO
(8) WEIGHTS
Shipping:
Operating:
SR
2
SN
 
4
15
Scroll
60 tons
SS
 
10
180
65
SN
 
3
144
SN
 
4"
4"
1"
4"
3"
SN
 
 

90 GPM
180 GPM
SN
 

256
128
103
SN
 
R-407C
SN
 

350 gal
450 gal
SN
 
82"
92"
96"
SN
 
5,155 lbs
9,515 lbs
 

Specification Notes:
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liabililty. Selection of certain optional features may change listed specifications.
2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40. The minimum recommended operating temperature when no glycol is used is 48°F.
3. Consult pump curve for exact pump performance.
4. Flow rate (GPM) is based on 60°F city water source with a clean condenser.
5. Flow rate (GPM) is based on 85°F tower water source with a clean condenser.
6. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
7. Consult factory for 50HZ operation.
8. Unit weight crated for shipment. 9. See Warranty Statement #W-700 for details.

Advantage Products
5 Steps to Complete Central Chiller Information
Return to Step 1 : Select Condenser
Return to Step 2 : Select Reservoir
Return to Step 3 : Select Capacity
Step 4 : View Unit Details
Step 5 : Get Pricing Now
Supporting Documents
Literature Literature
PDFPDF
2 Pages
Color
91 KB
Manual Manual
pdf logoPDF
56 pages
Color
520 KB
Knowledge Base
PDF HTML PDF & HTML
Documents covering the selection, service & operation of central liquid chillers.
American Flag Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142   Phone: 317-887-0729   Fax: 317-881-1277
Privacy Statement and Terms of Use.    Sitemap   Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability. Products are assembled in the United States of America.
©1998 - 2010 ADVANTAGE ENGINEERING, INC