Central Water Chiller : Water-Cooled
Model: TI-150W
Specifications
Have A Question?
Call 317-887-0729
for your answer.
--
PRODUCT SPECIFICATIONS
Model: TI-150W (1)
Refrigerant Zones
Quantity:
2
Compressor
Quantity:
2
HP:
80
Type:
Screw
(2) Total Capacity:
147 Tons
Refrigerant
Type:
R-407C
Water-Cooled Condenser
(3) City Water:
220.5 GPM
(4) Tower Water:
441 GPM
(5)(6) Process Pump
HP:
20
GPM:
360
PSI:
65
(5)(6) Evaporator Pump
HP:
10
GPM:
360
Reservoir Capacity
Operating:
1,200 gal
Holding:
1,475 gal
Connection Sizes
To Process:
6"
From Process:
6"
Water Make-Up:
1-1/2"
Overflow:
4"
Condenser:
4"
(7)(8) Full Load Amperage
230/3/60
496.0
460/3/60
248.0
575/3/60
199.0
Dimensions
Height:
112"
Width:
136"
Depth:
128"
Weight
(9) Shipping:
7,000 lbs
Operating:
20,500 lbs
Specification Notes::
1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 105°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40. The minimum recommended operating temperature when no glycol is used is 48°F.
3. Flow rate (GPM) is based on 60°F city water source with a clean condenser.
4. Flow rate (GPM) is based on 85°F tower water source with a clean condenser.
5. Consult pump curve for exact pump performance.
6. Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
7. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
8. Consult factory for 50HZ operation.
9. Unit weight crated for shipment.
10. See
Product Warranty Statement W-700 for details on warranty.

TI-150W shown.
Image shown is typical. Actual unit appearance will vary according to specifications and options.
Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142 Phone: 317-887-0729 Fax: 317-881-1277
Privacy Statement: we will not sell, rent or release any personal information you share with us to third party vendors.
Sitemap Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability.
Products are assembled in the United States of America.
© 2013 ADVANTAGE ENGINEERING, INC
Advantage Engineering Provides Industry Process Cooling Equipment For Optimizing Your Process